Manufacturer datasheetPDF · specs, listings and installationHighlights
Full details and specs- 135°F fixed plus rate-of-rise (15°F/min)
- Head only, base sold separately
- 50 ft spacing on smooth ceilings
- Low 80 µA standby current
- Two standby LEDs and built-in test switch
Get it Tue, Nov 10 – Fri, Nov 13UPS Ground, business days. Exact delivery cost is shown at checkout.
Free shipping on orders $250+Ships to all 50 states. Under $250, UPS Ground is calculated at checkout.
Buying for resale? Order tax-freeEmail your resale certificate (NY ST-120 or your state’s form) to support@reupsupplyco.com. We set your account tax-exempt, then you sign in at checkout.
Have a whole parts list?Paste it on Quick order and check out in one step. Parts we don’t list get a quote.
30-day returns on unopened itemsDelivery and returns
About this product
Plug-in heat detector head from System Sensor's 100 Series, with a 135°F fixed alarm point plus rate-of-rise sensing above 15°F per minute. The head is sold alone and mounts on a 100 or 400 Series base.
Rate-of-rise lets it alarm on a fast fire before the room reaches 135°F. Spacing is 50 ft (2,500 sq ft) on smooth ceilings, standby draw is only 80 µA, and two LEDs blink in standby for 360° visibility.
Photos show the head installed in a base for reference. The base is not included. Install, program and test per NFPA 72 and local code.
Key features
- 135°F fixed plus rate-of-rise (15°F/min)
- Head only, base sold separately
- 50 ft spacing on smooth ceilings
- Low 80 µA standby current
- Two standby LEDs and built-in test switch
What’s in the box
1 heat detector head. Base not included (photos show it mounted in a base).
Specifications
| Brand | System Sensor |
|---|---|
| Model | 5151 |
| Series | 100 Series plug-in thermal |
| Sensing | Fixed temperature plus rate-of-rise |
| Alarm point | 135°F (57.2°C) fixed; rate-of-rise above 15°F per minute |
| Voltage | 8.5 to 35 VDC |
| Standby current | 80 µA at 24 VDC |
| Compatible bases | B110LP, B110RLP, B112LP, B114LP, B116LP; B401 with F110 flange ring |
| Spacing | 50 ft (2,500 sq ft) on smooth ceilings |
| Height | 1.64 in |
| Diameter | 4.0 in |
| Application temperature | 32°F to 100°F (0°C to 38°C) |
| Humidity | 10 to 93% RH, non-condensing |
| Shipping weight | 2.8 oz |
| Approvals | UL, FM, CSFM |
| Selling unit | 1 detector head (base not included) |
| ReUp item | RU-SS-5151 |